A lower slate wing ends against a taller wall. The roofer measures the slope to order stone. The drainage designer needs two other measurements to check the leader, the pipe that takes water from the gutter. One comes from looking down at the wing on plan. The other comes from looking straight at the wall above it.
One example of the distinction appears in Wolfforth, Texas, Ordinance 2024-034. Section 1106.4 includes half the area of a vertical wall that sends rain to the roof when determining the contributing area for leaders and storm piping. A shaded roof polygon alone cannot show the height or extent of that wall.
Match the elevation to one outlet
Suppose a slate wing has a horizontal footprint of 600 square feet, all draining to one leader. A wall 20 feet wide and 12 feet high sheds its water onto that wing. On the cited basis, the wall is 240 square feet and its contribution is 120. The area to carry into that leader calculation is 720 square feet. The extra 120 belongs on the drainage worksheet. It buys no extra slate.
On a real elevation, outline only the part that discharges onto the area served by that outlet. If a canopy catches some of the water, trace its discharge before assigning that portion. Give the designer the marked plan, matching elevation and outlet identifier. The designer still needs the applicable local rule and rainfall criteria to select a pipe. For a collection-volume example that uses the same plan-view distinction, see which part of a slate roof fills one barrel.