A solar drawing specifies a 6 mm² conductor. The proposed roof flashing accepts cables from 4 to 8 mm. A quick glance puts six between four and eight. Look at the units again. Square millimetres describe the cross-sectional area of the conductor. The flashing seals around the outside of the finished cable, jacket included. The electrical schedule alone cannot tell the roofer whether the two will fit.
In its April 2026 solar brochure, DEKS lists a 4–8 mm range for its DNLS10MB multicable flashing. Suppose the cable supplier’s data sheet gives an overall diameter of 8.6 mm for the selected cable. That cable falls outside the listed range even if the conductor size on the drawing is 6 mm². A different cable with the same conductor area can have a different outside diameter.
Put both suppliers’ information on one sketch
At each proposed entry, identify the tile profile, roof slope, flashing model, cable part number and number of runs. Put the jacket diameter beside the manufacturer’s individual entry range. If the design routes the conductors inside a conduit through the roof, draw that conduit and send the changed detail back for selection. Its outside surface is what the roof detail must accommodate.
The electrical designer can confirm the cable and routing. The roofer can then check how the specified flashing fits the tile courses and underlying water-control layer. Record both answers before ordering. The affiliated Tile Roofing USA guide to roof penetrations gives context for reviewing the surrounding roof work.