On a concrete tile roof with a single ridge between two slopes, a ventilation worksheet may include a row for each slope. If both rows claim the full ridge exhaust, the sum can double the available opening on paper. Start by reading the unit attached to the manufacturer’s rating.
Ventco gives its TileVent and Universal Water Dam combination a net free area of 22 square inches per linear foot of ridge or hip. The measured item is a length along the assembled vent. Two roof planes meet there, but there is only one installed length to enter.
Mark the working length on the drawing
Suppose the approved detail shows 18 feet of working vent along a 24-foot ridge. At the published rate, that run contributes 18 × 22 = 396 square inches of nominal exhaust area. Using the full architectural ridge length would give 528. Giving both slopes credit for the same 18 feet would give 792. Neither figure describes the vent shown.
Give each physical run one identifier, mark the vented limits and record which attic space it serves. If a partition divides the attic, ask the designer how much of the run communicates with each compartment. Intake, clear air paths and the required area still need their own checks. Where the roof also has a powered fan, review the fan and ridge vent arrangement before totaling exhaust capacity.