A reroof that includes air sealing may come with blower-door reports from before and after the work. Before treating the difference as savings from the roof project, look for a floor plan and the position of every attic hatch. Two tests at the same pressure can include different parts of the building.
One house, two very different hatches
Building America researchers studied a Florida house with a tiled, unvented roof and upper and lower attics. At a reference pressure of 50 pascals, the reported airflow was 4,429 cubic feet per minute with both hatches closed. Opening just the upper hatch raised the result by 44. Opening just the lower hatch raised it by 583. The team also measured pressure differences between the house and the attic spaces. Those measurements helped explain how strongly each attic already communicated with the living space.
The 583 figure is a change in whole-building test flow. Assigning it all to a leaky hatch gasket would send the repair crew looking in the wrong place. Opening the hatch also changed the air paths between the test fan, that attic and outdoors.
What to keep with a reroof closeout
Ask the tester to mark each hatch, the air boundary intended by the design and the configuration used for each result. If the two reports show different hatch positions, have the tester explain which results can be compared or repeat a matched configuration. Keep observations about water entry in a separate record. For another question that depends on which attic a device actually serves, see the Guild guide to powered fans and tile ridge vents.