Which number on a slate vent sheet belongs in the fan calculation?

Match the proposed airflow to the pressure loss of the terminal before approving an in-line vent for a small-slate roof.

By the Slate, Tile & Metal Guild ·

A low-profile outlet can fit the slate courses on a drawing and still leave the bathroom fan with more resistance than its designer allowed. The same catalogue sheet may describe two uses, ventilating the roof space and terminating a duct. Start with the use shown on the mechanical plan.

Klober lists 6,500 square millimetres of effective vent area for its Mini Uni-Line, a fitting for small double-lap slates. For air moving through the terminal, it gives a different set of figures. At 15 litres per second the resistance is 24 pascals. At 30 litres per second it is 96 pascals. Doubling the design flow in that particular example quadruples the terminal loss. The area on the first line cannot stand in for either pressure value.

Put the fan duty beside the roof detail

For a proposed 30-litre-per-second extract, ask the mechanical designer to enter the terminal’s 96 pascals alongside the duct and fitting losses and check that duty against the fan curve. If capacity falls short, the designer can revisit the duct route, fan or terminal before the slater makes an opening. Ask the slater to confirm the selected model fits the actual slate dimensions and roof pitch. Record both checks against the same model number so a later substitution reaches both trades.

Where the project team needs a slater to review the proposed opening, use the Slate Roofing USA directory to identify firms to consult.

Further reading

Klober · Mini Uni-Line Slate Vent, KG9631 technical data. The figures are specific to this UK terminal. A mechanical designer must evaluate the complete duct route.