Two single-slope roofs can have identical pitches and very different distances from high point to eaves. An elevation marked only with the angle leaves out a dimension the tile manufacturer may use to qualify its minimum pitch.
Marley gives a specific UK example for its Mendip 12.5 concrete interlocking tile. At the stated minimum of 12.5 degrees, the cited combination is a 100 mm headlap and a rafter up to 6 m long. Consider two drawings, one with a 5.8 m rafter and the other with a 6.4 m rafter. Both show that angle and lap. The shorter one fits those three published dimensions. The longer one falls outside that example even though its pitch annotation looks identical.
Read the section drawing
Trace the sloping rafter dimension on the section. A plan dimension may give the horizontal projection, which gets shorter than the rafter as pitch increases. Record the drawing revision and note any change in slope. Ask the designer to resolve an overlength condition before the purchase order goes out.
For a US project, obtain the limits and approvals for the exact locally proposed tile. The UK product example illustrates how to read a conditional limit. Include the accepted profile, rafter length, slope and headlap in the tile takeoff so a later substitution triggers a fresh check.