Concrete tile · Attic ventilation

Four tile vents on the drawing. How much open area do they provide?

Use a manufacturer’s profile-specific vent ratings to check a concrete tile roof schedule before ordering.

By the Slate, Tile & Metal Guild ·

Four identical vent symbols can survive several drawing revisions even after the specified roof tile changes. That matters when a vent cover follows the shape of the field tile. Before ordering, look up the net free ventilation area for the profile and mesh actually quoted. The outside width and height of the cover will not give you that number.

Check one row of the schedule

O’Hagin lists 88.87 square inches for its flat Fire&Ice tile vent with one-eighth-inch mesh and 77.63 square inches for the M-profile version in the same table. Suppose a designer has assigned 320 square inches of exhaust to one attic zone. Four flat units total 355.48 square inches. Four M-profile units total 310.52, leaving that schedule 9.48 square inches short of the assigned amount. The drawings might show the same symbol count, yet the substitution changes the result.

That 320-square-inch target is hypothetical. It says nothing about the target for another attic. If the actual tile requires the M profile, send the discrepancy to the designer before buying vents. The flat version’s higher figure does not make it a compatible substitute. Adding one unit on paper also leaves its position, the available intake and the area it serves to be checked.

Make the change visible to the roofer

Write the model, profile, mesh, area per vent and quantity beside the zone designation. Keep intake and exhaust on separate lines. If two attic compartments do not communicate, a surplus assigned to one should not hide a shortfall on the other’s schedule. Ask the project designer to sign off on the revised layout and retain the product sheet used in the calculation. For an owner investigating dampness after occupancy, Tile Roofing USA’s condensation and leak guide explains what observations to collect.