Preserving the craft. Building its future.

Concrete tile · Reading fire classifications

Does Class A supply the missing hour rating on a concrete tile roof schedule?

Trace the direction of fire exposure before using a roof-covering test to complete a roof-and-ceiling schedule.

By the Slate, Tile & Metal Guild ·

A drawing has two empty cells beside the roof above a corridor. One asks for the roof covering’s fire classification. The other asks for the fire-resistance rating of the roof-and-ceiling construction in hours. A supplier submits a Class A report for a concrete tile roof covering. Which cell can the report help fill?

Look at the exposure in ASTM E108. Fire is applied outside the building. Among other things the test evaluates flame spread over the roof surface and penetration toward the underside of the deck. Class A describes performance under the specified severe exterior exposure. The letter has no conversion into minutes of resistance to a fire originating in the corridor below. Section 4.5 of the standard expressly limits what the test establishes about a fire starting inside.

Trace the two paths on one section

On a copy of the drawing, put one arrow at the outer tile surface and a second below the finished ceiling. Attach the covering report to the first arrow. Identify the covering, deck and other conditions it describes so the design team can compare them with the proposed roof. The Tile Roofing USA guide to assembly documentation outlines what to keep in that record.

For the second arrow, ask the architect whether an hourly rating is required there and which assembly detail or design establishes it. Leave the field open pending that answer. This keeps a valid exterior test report in the file and makes the outstanding ceiling question visible before the drawings go out for pricing.

Further reading

ASTM International · E108, Standard Test Methods for Fire Tests of Roof Coverings, sections 1 and 4. The published scope describes an exterior exposure test. Project requirements and the applicable assembly evidence belong with the designer.

Published by the Guild as part of Tim Kelly’s Slate Boss resource network. These educational guides support project conversations and do not replace an on-site inspection or a project specification.

← All roofing articles